by KEMPER
The KEMPER ’Multi-Fix’ manual double regulating valve is designed for use on recirculating secondary hot water systems allowing the water temperature to be measured and adjusted. The ’Multi-Fix’ is part of the KEMPER range of valves which includes the ’Multi-Therm’, ’Eta-Therm’ and ’Multi-Tee’ designed to maintain the secondary re-circulating return water at 58°C.
Traditionally a commissioning set or a thermometer and double regulating valve have been used to control the fl ow but site condition can necessitate small changes in installation which affect the heat loss from the system. The ’Multi-Fix’ valve combines a double regulating control valve with a temperature pocket and thermometer into one valve for ease of installation and use. The valve should be installed at the end of the least favoured branch (furthest away) of a multi branch system to ensure the water is at the desired temperature.
This download includes the all size variations for the Multi-Fix Manual Circulation Regulating Valve by KEMPER.
Read more1 Revision
24/11/2014
Compliant
Compliant
Not Available
Not available.