SIDERISE RF raised access floor system has been specifically developed to provide cavity fire stops for use in voids between raised access floors and floor slabs. It is designed as a one-piece system and allows easy cutting and installation. The product also offers unique vertical compression to allow tightness of fit.
SIDERISE RF-CB cavity barrier systems:
Used to subdivide uninterrupted voids in accordance with Building Regulations offering 30 minutes fire resistance, (EI 30). CB barriers are designed to suit individual floor void depths of 50–600 mm.
SIDERISE RF-FS fire stop systems:
Maintains continuity of fire resistance for installations aligned with fire rated partitions, hence maintaining compartmentation. The FS system offers 60–120 minutes' fire resistance. FS barriers are designed to suit individual floor void depths of 50–600 mm.
Features and benefits:
Economical and easy to install.
Fully qualified acoustic performance
Provides a smoke and fire seal.
Provides excellent lateral compression.
Provides up to 120 minutes' fire integrity and insulation.
Quality assured to BS EN ISO 9001.
Suitable for use in air plenum applications.
Suitable for use in voids heights up to 600 mm as standard.
Supplied in sheet form, for cutting on-site, or pre-cut in strips to suit specific void height.
Fire resistance tested to principles of EN 1366-4