Single unit Y-Pattern globe valves incorporating an integral orifice plate to form a fixed orifice flow measurement unit with regulation and isolation capacity
The Double Regulating feature allows the valve to be used for isolation and to be reopened to its pre-set position to maintain required flow rate
Accuracy of flow measurement is ±5% at all open positions of the valve in accordance with BS 7350: 1990
Primarily used in injection or other circuits requiring a double regulating valve for system balancing
Size | DN65 to DN300 |
Pressure Rating | Class 125 |
Flow Rate | Please see Flow Measurement Graphs |
Temperature Rating | 10 - 120°C |
End Connections | Flanged connections - ANSI Class 125 |
Material | Ductile Iron |
1 Revision
06/10/2021
Compliant
Compliant
Not Available
Not available.
There are no EPDs.